Pipe Network Type

5.6Mpa Heptafluoropropane Fm200 Fire Extinguishing System

Description : Pipe network fm200 fire suppression device is composed of the following components: fm200 agent, fm200 cylinders, container valves, flexible hoses, liquid flow check valves, a set of manifold, a safety valve, pressure switch,...
Products Inquiry

Description

Description:
Pipe network fm200 fire suppression device is composed of the following components: fm200 agent, fm200 cylinders, container valves, flexible hoses, liquid flow check valves, a set of manifold, a safety valve, pressure switch, nitrogen driving device(s), driving device frame, gas control pipe, gas flow check valves(it depends), selective valves(it depends), a pair of elbows and flanges, nozzles.
 
Product Application:
. High-tech medical;
. Robotic equipment;
. Telecommunication centers;
. Textile manufacturing;
. Records and data archives;
. Electric utility facilities;
. Testing/imaging equipment;
. Media storage;
. Chemical laboratories;
. Military vehicles.
 
Attentions:
. Choice for storage room, including ambient environment and volume;
. Design of pipeline, including placement of conduits and connection;
. Installation, integration of each parts and connection between parts
. A separated room needed for storage.
 
Product Parameter:
No. specification Technical Parameter
1 Filling pressure 5.6Mpa
2 Scale of Protective region for one zone area:max single-zone is 800m² volume:max single-zone is 3600m³
3 Spraying time ≤10s
4 Filling density ≤1080kg/m3
5 power DC24V/1.6A
6 Nitrogen Pressure of Driving Device 6.0±1.0Mpa(20℃)
7 Condition of reserving room for container temperature: -10~50℃, relative humidity: ≤97%
8 max working pressure 8.0Mpa
9 min working pressure 4.6Mpa